Integration, versatility and control: why choose BiniClima FQH-EC in professional projects
A compact and silent fan coil designed to integrate into high-efficiency professional systems and home automation

In the context of professional air conditioning, design needs are evolving: today it is no longer enough to offer high performance, but it is necessary to guarantee architectural integration, system flexibility and intelligent control of comfort . The FQH-EC ductable fan coil by BiniClima responds to this challenge with a series of solutions designed to adapt to multiple installation scenarios, simplify maintenance and integrate into advanced home automation logics.
Compact unit, modular components: designed for easy installation
FQH-EC is a machine designed to simplify the work of designers and installers . The unit is completely made of galvanized sheet metal, with class 1 fireproof insulation in strategic points (battery and ventilation section), and features a “drawer” configuration that allows quick access to the ventilation section, which can be removed with just two screws.
An important strong point is the on-site modifiability of the hydraulic connections , which can be arranged on the right or left side depending on the design needs. The air filter, which can be integrated into the plenum or accessed from below, has also been designed for easy maintenance in environments with false ceilings or in situations where space is limited.
Electronic control and compatibility with automation systems
The presence of the EC motor with 0–10 V signal, supported by self-lubricating bearings, IP65 protection and explosion-proof functionality, allows not only to reduce consumption (below the ErP2015 limits), but also to precisely optimize the ventilation speed based on the thermal load. It is a fundamental element for integration in centralized systems, where dynamic control of the flow rates allows to maximize the overall performance.
The system is designed for connection to digital thermostats and Wi-Fi, even in master/slave mode via Modbus or Bacnet protocol , responding to the needs of integration with BMS systems in the hotel, management or healthcare sectors.
Maximum hygiene and air quality in sensitive environments
In environments such as hospitals , schools or hotel rooms , air quality is a priority. FQH-EC is designed to be combined with external air intakes and centralized primary air treatment systems, improving air exchange and contributing to the control of humidity and CO₂ in closed environments.
The regenerable air filter in synthetic material, with EU2-G2-M2 efficiency (EN 779), and the possibility of installing aluminium or washable filters, offer a wide choice to adapt the filtration to the type of environment served.
Silence and comfort: certified acoustic performance
Another distinctive aspect is the attention to acoustic performance, thanks to the insulation with APLOB sound-absorbing material and the availability of sound-absorbing accessories up to 20 mm. In the minimum configuration, the sound pressure level is less than 22 dB(A) , making FQH-EC suitable for use in spaces where acoustic comfort is essential, such as hotel rooms or professional studios.
A professional solution designed to last
With AHRI certified copper and aluminum coils , insulated condensate tray painted on both sides, double inclined drains and a wide range of accessories (valves, thermostats, plenum panels), FQH-EC confirms itself as a reliable and durable solution . Operating temperatures up to 100°C and tested operating pressure up to 20 bar guarantee the robustness of the system even in intensive conditions.
Common data | UM | 03 | 04 | |
---|---|---|---|---|
Power absorbed | Max | W | 12.3 | 19 |
Absorption | TO | 0.08 | 0.14 | |
Sound power (Lw) | Max (4) | dB(A) | 40.7 | 44.0 |
Sound pressure (Lp) | dB(A) | 32.7 | 36.0 | |
Sound power (Lw) | Med (4) | dB(A) | 31.9 | 34.2 |
Sound pressure (Lp) | dB(A) | 23.9 | 26.2 | |
Sound power (Lw) | Min (4) | dB(A) | 29.0 | 29.8 |
Sound pressure (Lp) | dB(A) | 21.0 | 21.8 | |
Battery length | 10T=H250mm | mm | 600 | 800 |
Battery front surface | 3R-10T | m² | 0.15 | 0.20 |
Water content | 3R-10T | lt | 1.38 | 1.83 |
Electric element | EE-V230 | W | 1000 | 1500 |
High capacity electric el. | EH-V230 | W | 1200 | 2000 |